GCK(L) Low Voltage Draw-out Switchgear Cabinet is composed of power distribution center (PC) cabinet and motor control center and is applicable to power plants, transformer substations and industrial and mining enterprise. It is used in power distribution system at AC 50Hz, maximum working voltage of 660V and maximum working current of 3150A for power transformation, distribution and control of motor power, motor control and lighting.
Technical Parameters:
Rated working frequency(Hz) | 50 | |
Rated working voltage(V) | 380 | |
Rated insulated voltage(V) | 660 | |
Maximum rated working current(A) | Horizontal busbar | 630-4000 |
Vertical busbar | 1600 | |
Maximum rated short-time withstand current | vertical busbar | 80kA(virtual value/1 second) |
Vertical busbar | 50kA(virtual value/1 second) | |
Maximum rated peak withstand current | Horizontal busbar | 170kA |
Vertical busbar | 110kA | |
Plug-in for major circuit(A) | 200/400/630 | |
Plug-in for Ancillary circuit(A) | 10 | |
Power frequency 1min(A) | 2500 | |
Maximum capacity of motor control(kW) | 155 | |
Protection class | IP30~IP40 | |
Operating model | On the spot, in the distance, auto-adjustable |